How much electricity can chemical-free cooling-tower treatment actually save? Instead of quoting percentages in the abstract, here is a worked example for a typical Thai installation: one 720 TR water-cooled chiller with a 1,000 TR cooling tower, treated with Elgressy EST (Electrolysis Scale Treatment).
Short answer: running 24/7, EST saves about 207,500 kWh and roughly 870,000 THB of electricity per year, and avoids about 104 tonnes of CO₂.
Why scale costs energy
A chiller rejects its heat through the condenser, which is cooled by the cooling-tower water. When hardness in that water deposits as calcium carbonate scale on the condenser tubes, it acts as insulation. Heat transfer drops, the condensing pressure rises, and the compressor has to work harder to deliver the same cooling. Even a thin scale layer is enough to push up the chiller’s kW per TR.

Elgressy EST removes the hardness in a side-stream reactor, where an electric current makes the scale form on the reactor wall instead of on your condenser. The scale is scraped off and flushed out automatically, so the condenser tubes stay clean and the chiller keeps running at its design efficiency. Across installations, this gives an average energy saving of 6.75% or more on the chiller.
The example: 720 TR chiller, 1,000 TR cooling tower
Assumptions used:
- Chiller efficiency 0.65 kW/TR (typical water-cooled chiller)
- Average load 75% of capacity, i.e. 540 TR
- Electricity price 4.2 THB/kWh
- EST energy saving 6.75% (average)
- Grid emission factor 0.50 kg CO₂ per kWh
| 720 TR chiller | 24/7 operation (8,760 h) | 12 h per day (4,380 h) |
|---|---|---|
| Average power | 351 kW | 351 kW |
| Energy without EST | 3,074,760 kWh/yr | 1,537,380 kWh/yr |
| Electricity cost without EST | 12.9 million THB/yr | 6.46 million THB/yr |
| Energy with EST | 2,867,214 kWh/yr | 1,433,607 kWh/yr |
| Energy saved | 207,546 kWh/yr | 103,773 kWh/yr |
| Money saved | ≈ 871,700 THB/yr | ≈ 435,800 THB/yr |
| CO₂ avoided | ≈ 104 tonnes/yr | ≈ 52 tonnes/yr |
The saving above is on the chiller compressor only. The 1,000 TR cooling tower is larger than the chiller needs, which is good: it delivers colder condenser water. Tower fans and pumps are not included in the figures.
More than energy
Energy is only part of the return. With EST the cooling tower also runs without scale inhibitors, biocides or acid dosing, and at higher cycles of concentration, so it uses less make-up water and discharges less blowdown. EST is a one-time investment with a small footprint, low maintenance and no chemical deliveries, and thanks to its long service life the savings over its lifetime are typically more than five times the investment.

EST also supports green-building credits for LEED and WELL projects. Read more in our guide to non-chemical water treatment in Thailand.
What will EST save on your chiller?
Every site is different. Your real saving depends on your chiller’s actual kW/TR, its running hours and your electricity tariff (especially on a time-of-use rate). Send us those three figures and we will prepare a free, site-specific energy and ROI calculation, including EST price and payback.
Contact Water Treatment Asia: dja@watertreatmentasia.com · English 064 284 6598 · Thai 063 957 8383
The figures in this example are estimates based on the assumptions listed above and an average saving of 6.75%. Actual savings depend on site conditions.


Leave A Comment